Terminal HEPA Filters – OQ Protocol

Operational Qualification Protocol for Terminal HEPA Filters

Document Number: OQ-THF-001

Version: 1.0

Effective Date: [Insert Date]

Reviewed By: [Insert Name]

Approval Date: [Insert Date]

Objective

The objective of this Operational Qualification (OQ) protocol is to verify that the Terminal HEPA Filters used in the engineering area meet the defined acceptance criteria for HEPA filtration in Grade A/B environments as per ISO 14644 Annex 1.

Scope

This protocol applies to the Terminal HEPA Filters utilized in the sterile manufacturing area for injectables/aseptic processes. It encompasses the qualification activities necessary to ensure compliance with regulatory requirements.

Responsibilities

The following personnel are responsible for the execution and oversight of this protocol:

  • Validation Team: Execution of the OQ protocol
  • Quality Assurance: Review and approval of the protocol
  • Engineering: Maintenance and operation of the equipment

Prerequisites

  • Completion of Installation Qualification (IQ) for Terminal HEPA Filters.
  • Availability of all necessary equipment and materials for testing.
  • Training of personnel on OQ procedures.

Equipment Description

The Terminal HEPA Filters are designed to provide high-efficiency particulate air filtration for Grade A/B environments, ensuring the removal of airborne contaminants to maintain sterility during the manufacturing of injectable products.

Test Plan

Test ID Procedure Acceptance Criteria Evidence
OQ-THF-01 Integrity Leak Test No leaks detected Test report
OQ-THF-02 Airflow Face Velocity Measurement Within specified limits as per ISO 14644 Annex 1 Measurement logs

Detailed Test Cases

Test ID: OQ-THF-01

Procedure: Perform an integrity leak test using a suitable method (e.g., DOP test) to ensure no leaks are present.

See also  Depot Suspension Preparation Vessel – Validation Summary Report (VSR) Template

Acceptance Criteria: No leaks detected.

Evidence: Documented test report indicating results.

Test ID: OQ-THF-02

Procedure: Measure the airflow face velocity across the HEPA filter using a calibrated anemometer.

Acceptance Criteria: Airflow face velocity must be within specified limits as per ISO 14644 Annex 1.

Evidence: Measurement logs and calibration certificates of the anemometer.

Deviations

Any deviations from the established procedures or acceptance criteria must be documented and justified. A deviation report should be submitted for review and approval.

Approvals

By signing below, the undersigned acknowledge the review and approval of this Operational Qualification Protocol.

_________________________
Validation Team Lead

_________________________
Quality Assurance Representative

_________________________
Engineering Representative