AHU for Aseptic Area – PQ Protocol

Document Number: PQ-001

Version: 1.0

Effective Date: YYYY-MM-DD

Reviewed By: [Name]

Approval Date: YYYY-MM-DD

Performance Qualification Protocol for AHU in Aseptic Area

Meta Description: This document outlines the Performance Qualification protocol for the Air Handling Unit (AHU) serving the Aseptic Area, ensuring compliance with industry standards.

Tags: Equipment Validation, Performance Qualification, Aseptic Area, HVAC

Objective

The objective of this Performance Qualification (PQ) protocol is to verify that the Air Handling Unit (AHU) serving the Aseptic Area operates within defined specifications and meets the acceptance criteria outlined in the User Requirement Specification (URS) and relevant regulatory guidelines.

Scope

This protocol applies to the performance qualification of the AHU utilized in the sterile manufacturing process for injectables. It encompasses testing of critical parameters to ensure compliance with regulatory standards.

Responsibilities

  • Validation Team: Responsible for executing the PQ protocol and documenting results.
  • Quality Assurance: Responsible for reviewing and approving the PQ protocol and results.
  • Engineering: Responsible for maintaining the AHU and providing necessary documentation.

Prerequisites

  • Completion of Installation Qualification (IQ) and Operational Qualification (OQ).
  • Availability of necessary documentation including URS, SOPs, and maintenance logs.
  • Calibration of measurement instruments used in testing.

Equipment Description

The Air Handling Unit (AHU) is a utility system designed to provide filtered and conditioned air to classified rooms in the aseptic manufacturing area. It ensures that the critical parameters of airflow, temperature, relative humidity (RH), differential pressure (DP), alarms, trends, and audit trails are maintained within specified limits.

See also  Split Butterfly Valve (SBV) Transfer System – Qualification Certificate Template

Test Plan

Test ID Procedure Acceptance Evidence
TP-01 Measure ACH ≥ 20 ACH Calibration report, measurement logs
TP-02 Measure Airflow Within specified range Flow meter readings
TP-03 Measure Temperature 20°C – 24°C Temperature logs
TP-04 Measure RH 30% – 60% Humidity logs
TP-05 Check DP Within specified limits DP gauge readings
TP-06 Verify Alarms All alarms functional Alarm test log
TP-07 Review Trends No anomalies Trend analysis report
TP-08 Audit Trail Review Complete and accurate Audit trail report

Detailed Test Cases

TP-01: Measure ACH
Procedure: Use an anemometer to measure air changes per hour (ACH) in the classified room. Document the readings and calculate the ACH based on room volume.
Acceptance Criteria: ACH must be ≥ 20.
Evidence: Measurement logs and calculation documentation.

TP-02: Measure Airflow
Procedure: Measure airflow using calibrated flow meters at designated locations. Ensure readings are within specified operational ranges.
Acceptance Criteria: Must be within specified range.
Evidence: Flow meter readings documentation.

Deviations

Any deviations from the acceptance criteria must be documented in a deviation report and reviewed by the Quality Assurance team. Justifications for deviations must be provided and corrective actions must be implemented.

Approvals

Prepared By: [Name]   Date: YYYY-MM-DD

Reviewed By: [Name]   Date: YYYY-MM-DD

Approved By: [Name]   Date: YYYY-MM-DD