| URS ID | URS Statement | Risk (H/M/L) | DQ Test Ref | IQ Test Ref | OQ Test Ref | PQ Test Ref | Evidence/Record | Result |
|---|---|---|---|---|---|---|---|---|
| URS-001 | The dispensing booth shall maintain a minimum air velocity of 0.45 m/s at the work surface. | H | DQ-001 | IQ-001 | OQ-001 | PQ-001 | Air velocity test report | Pass |
| URS-002 | The HEPA filter integrity must be verified before each use. | H | DQ-002 | IQ-002 | OQ-002 | PQ-002 | HEPA integrity test report | Pass |
| URS-003 | The dispensing booth must have differential pressure (DP) alarms that activate at set thresholds. | M | DQ-003 | IQ-003 | OQ-003 | PQ-003 | DP alarm test report | Pass |